DoD

DoD (depth of discharge) states how much of the nominal capacity is actually withdrawn: 90 % DoD on 200 kWh means 180 kWh are used.

What does DoD mean?

Depth of Discharge states how much of the nominal capacity is actually withdrawn. 90 % DoD on 200 kWh means: 180 kWh are used, 20 kWh remain in the cell as a reserve.

Modern LFP systems permit high depths of discharge (sometimes 100 % per datasheet), but DoD remains a design lever: cycling shallower slows ageing — exhausting the warranted capacity is paid for in lifetime.

What matters in practice

  • usable capacity = nominal capacity × DoD — calculate with nothing else
  • datasheet DoD and warranty DoD can differ
  • a backup reserve reduces the everyday usable depth of discharge
  • respect BMS limits: deep discharge is a damage event

Practical example

A system “with 215 kWh” runs 90 % DoD in daily operation and holds a 30 % backup reserve. Effectively it shifts about 130 kWh per day — that number, not the 215, belongs in the economic analysis.