Skip to content

Elecnova · Liquid cooling · 20-Fuß-Container

Elecnova ECO-B/Z20FT5015LP

Liquid-cooled 20 ft battery container: 5.015 MWh, LFP 314 Ah — for grid-scale storage, generation plants and large C&I projects; variants with 1 or 12 output circuits.

Elecnova ECO-B/Z20FT5015LP

Technical data

System
Nominal capacity 5.02 MWh
Cell type LFP 314 Ah
Cooling Liquid cooling
Form factor 20-Fuß-Container
Cycle life 8,000
Max. depth of discharge 100 %
Efficiency (RTE) 87 %
Grid & power
On/off-grid switching No
Direct PV input No
Installation
Dimensions (W×D×H) 6058×2438×2896 mm
Weight 41.8 t
IP rating IP55
Fire protection Aerosol + Wassersprühsystem

Technical data per the manufacturer's datasheet; binding values depend on configuration and project.

Powerful 20 ft ESS container solution with integrated pack, EMS, BMS, HVAC and fire-suppression system. Suited to utility, grid and large commercial and industrial storage applications with high power and flexible capacity. The container is a DC block connected via external power conversion — for example the Sinexcel converter and transformer systems from our range. Two variants are available: ECO-B20FT5015LP with one output circuit and ECO-Z20FT5015LP with twelve.

Frequently asked questions

Which applications is the ECO-B/Z20FT5015LP designed for?

The 20 ft battery container targets utility, grid and large commercial and industrial storage applications with high power and flexible capacity. Pack, EMS, BMS, HVAC and fire-suppression system are already integrated.

What capacity and cell technology does the container use?

5.015 MWh in a 12P416S system configuration based on 314 Ah LFP cells; one pack holds 104.5 kWh. Cycle life per the datasheet is at least 8,000 cycles, with an RTE of up to 87 %.

Does the container need external power conversion?

Yes. The container is built as a DC block and is connected via external power conversion — for example the Sinexcel converter and transformer systems from our range.

How do the ECO-B and ECO-Z variants differ?

The ECO-B20FT5015LP has one output circuit, the ECO-Z20FT5015LP twelve.

How is the container cooled and under which conditions does it operate?

Liquid cooling combined with forced air cooling; operating temperature −25 °C to +55 °C (derating above 45 °C), IP55 protection, corrosion class C4 (C5 optional), installation altitude up to 3,000 m.