Elecnova ECO-E418LP-A40/69/80

Liquid-cooled all-in-one storage cabinet: 418 kWh on a 2 m² footprint, 125 kW at 400 V (A40), 215 kW at 690 V (A69) or 210 kW at 800 V (A80).

Elecnova ECO-E418LP-A40/69/80

Technical data

System
Nominal capacity 418 kWh
Cell type LFP 314 Ah
Cooling Liquid cooling
Form factor Schrank
Cycle life 8,000
Max. depth of discharge 100 %
Efficiency (RTE) 89 %
Grid & power
AC power 215 kW
On/off-grid switching No
Direct PV input No
Installation
Dimensions (W×D×H) 1500×1350×2400 mm
Weight 3.8 t
IP rating IP55
Fire protection Aerosol

Technical data per the manufacturer's datasheet; binding values depend on configuration and project.

ECO-E418LP — 418 kWh in one cabinet

The ECO-E418LP is an all-in-one storage cabinet from Elecnova: battery, inverter (PCS), liquid cooling and aerosol fire suppression sit in one enclosure measuring 1,500 × 1,350 × 2,400 mm. That is around 2 m² of footprint for 418 kWh.

For comparison, the ECO-E261LP-2A from the same family fits 261 kWh on 1.4 m². At the same height, the E418LP is 450 mm wider and stores around 60 % more energy. Sites that need more capacity can therefore manage with fewer cabinets.

Three variants, one battery

The three models differ only on the AC side. Battery, cabinet, cooling and fire protection are identical:

VariantAC powerAC voltageGrid typeCharge/discharge rate
ECO-E418LP-A40125 kW400 V3W+N+PE / 3W+PE0.3 P
ECO-E418LP-A69215 kW690 V3W+PE0.5 P
ECO-E418LP-A80210 kW800 V3W+PE0.5 P

The A40 works at 400 V and so matches the usual low voltage in commercial buildings. The A69 and A80 work at 690 V and 800 V; they are connected via a transformer and are intended for projects in which a dedicated transformer station is planned anyway.

The variants also differ in the ratio of power to capacity. With the A40 (0.3 P), the full capacity lasts a little over three hours at rated power as a calculation; with the A69 and A80 (0.5 P), around two hours. The A40 therefore suits longer, flatter load phases, the other two higher peaks. More on this under C-rate.

Cooling and cells

Cooling is liquid-based at pack level, supplemented by forced air. According to the manufacturer, the temperature difference between cells stays below 3 °C. Even cell temperatures are a precondition for the stated cycle life of at least 8,000 cycles; see also air cooling vs. liquid cooling.

The battery consists of eight packs of 52.248 kWh each with LFP cells (314 Ah), connected in series as 1P416S at a rated voltage of 1,331.2 V.

Installation

At 3,800 kg, the E418LP is one of the heavier cabinets. The foundation and the load-bearing capacity of the ground should therefore be clarified early. The datasheet also states:

  • operating temperature −25 to 55 °C, with power derating above 45 °C
  • installation altitude up to 3,000 m, with derating above 2,000 m
  • IP55 protection, corrosion protection C4 (C5 optional)
  • noise level at most 80 dB

For the installation site this means that weight and noise belong in the site planning from the start, for example in the distance to noise-sensitive areas.

Technical key data

FeatureECO-E418LP-A40/69/80
Battery capacity418 kWh (8 × 52.248 kWh)
Cell chemistryLFP, 314 Ah
Configuration1P416S
Rated DC voltage1,331.2 V (1,164.8–1,497.6 V)
Charge/discharge rate0.3 P (A40) · 0.5 P (A69, A80)
Depth of discharge100 % (at 25 ± 2 °C)
Cycle life≥ 8,000 cycles
Round-trip efficiencyup to 89 %
AC power125 kW (A40) · 215 kW (A69) · 210 kW (A80)
AC voltage400 V · 690 V · 800 V, −15 to +10 %
Grid frequency50/60 Hz
Power factor0.99 / −1 to +1
THDi≤ 3 %
Coolingliquid cooling + forced air
Operating temperature−25 to 55 °C (derating above 45 °C)
Installation altitudeup to 3,000 m (derating above 2,000 m)
Humidity0–95 % (non-condensing)
Protection ratingIP55
Corrosion classC4 (C5 optional)
Fire protectionaerosol
Noise level≤ 80 dB
CommunicationModbus TCP/IP
Dimensions (W×D×H)1,500 × 1,350 × 2,400 mm
Weight3,800 kg
StandardsUN 38.3, IEC 62619, IEC 63056, IEC 62477-1, IEC 61000-6-2/4
Grid connectionEN 50549-1/-10, EN 50549-2/-10, PN-EN 50549-1/-2

Assessment

The E418LP is of interest when a business needs more than the 261 kWh of an E261LP but does not yet want to install a container. It is not a hybrid system: a PV system is connected via its own inverter on the AC side (AC coupling). This also makes it suitable for retrofitting to existing PV systems.

The variant has to be settled in every project: it depends on the voltage at the connection point and on whether power or duration matters more. In Austria, the classification under the TOR Erzeuger also belongs in the planning early on, together with the grid operator.

Frequently asked questions

What is the ECO-E418LP?

A liquid-cooled all-in-one storage cabinet from Elecnova with 418 kWh, a built-in inverter (PCS) and aerosol fire suppression. It stands on around 2 m² and weighs 3,800 kg.

How do the A40, A69 and A80 differ?

Only on the AC side. The A40 delivers 125 kW at 400 V, the A69 215 kW at 690 V and the A80 210 kW at 800 V. Battery, cabinet, cooling and fire protection are the same in all three variants.

Which variant suits a 400 V connection?

The A40: it works at 400 V and, according to the datasheet, supports both 3W+N+PE and 3W+PE. The A69 and A80 work at 690 V and 800 V and are connected to the grid via a transformer.

How long can the system discharge at full power?

As a calculation, a little over three hours for the A40 (418 kWh at 125 kW, charge/discharge rate 0.3 P) and around two hours for the A69 and A80 (0.5 P). The actual duration depends on operation, temperature and reserves.

Which grid connection standards does the datasheet list?

EN 50549-1/-10 and EN 50549-2/-10, plus the Polish edition PN-EN 50549-1/-2. In Austria, the classification under the TOR Erzeuger must also be clarified with the grid operator, who decides on the registration in each case.